Sampling Details | |||
---|---|---|---|
Sub Type: Hotel/motel | Special Feature: | Location: | |
Area: 490 | Volume (gallons): 12795 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 27 |
Disinfectant: Calcium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 0.6 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0.6 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 84 | pH: 7.8 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A)(1) / Public swimming pool shall be licensed
The Swimming Pool license could not be located. Locate, then post the current Swimming Pool license.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat The pool free chlorine residual was noted at 0ppm. Increase the residual to 1.0ppm minimum.
Mr. Polston agreed to Close the pool.
Correct By: 17-Oct-2023 3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat The filter system flow meter is not working. Repair the flow meter.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat The pool free chlorine residual was noted at 0ppm. Increase the residual to 1.0ppm minimum.
Mr. Polston agreed to Close the pool.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 17-Oct-2023
Comments |
---|
Pool Notes: 1. All necessary safety equipment is available. 2. New disinfectant system information was obtained.. 3. The pool water was clear. 4. Mr. Polston stated the facility does receive service notifications from ECOLAB. 5. ACC unit pH reads 7.48. 6. The report was emailed to the facility. Contact Scott Bradley,R.E.H.S. (732-7614) with any questions. |