Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 150 Volume (gallons): 1000 Flow measure reading (gpm): 40 Minimum required flow (gpm): 8
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 723 Turnover Rate (min): 120
Total Chlorine (ppm): 7 Free Chlorine (ppm): 7 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 30 Pool water temp ˚F: 80 pH: 7.2 Cyanuric acid (ppm): 30
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 34 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity reading of 30 ppm was less than the 60 ppm minimum established by code.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 31-July-2017

Comments
Facility inspection notes:
Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time.
Signage and safety equipment provided as required.
Restrooms are clean and properly supplied.
Pool looks good. Please keep up the good work.