Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1000 Volume (gallons): 30000 Flow measure reading (gpm): 50 Minimum required flow (gpm): 60
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 689 Turnover Rate (min): 480
Total Chlorine (ppm): 2.5 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 83 pH: 7.5 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Observed flow rate of 50 gpm is 10 gpm less than required to achieve 8 hour turnover.
Throttle the flow (if possible) to at least 60 gpm. If this is not possible, have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 23-August-2016

Comments
Facility inspection notes:
Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time.
Signage and safety equipment provided as required.
Monthly ACC pressure switch test is being documented in the pool records as required.
Restrooms are clean and properly supplied.
Pool looks great! Thanks for your time and efforts this pool season.