Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 880 | Volume (gallons): 26400 | Flow measure reading (gpm): | Minimum required flow (gpm): 55 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): | Free Chlorine (ppm): 10 | Combined Chlorine (ppm): | Total Bromine (ppm): |
Alkalinity (ppm): 140 | Pool water temp ˚F: 77 | pH: 7.8 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(j) / All SVRS devices are maintained/ functional and tested
When tested, the VACLERT device did not work.
Repair the device. Correct By: 24-Jun-2014 3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Specifications for the main drain covers has not been submitted at the Health District.
Provide specifications (Manufacturer, Model, Installation and Replacement Dates) for the main drain cover. Correct By: 24-Jun-2014 3701-31-04 (E)(3)(d) / "WARNING or DANGER - POOL CLOSED" sign(s) posted-when the pool is closed
The pool was closed but the "WARNING or DANGER - POOL CLOSED" sign was not posted.
Provide a sign stating "WARNING or DANGER - POOL CLOSED" . Correct By: 24-Jun-2014
Comments |
---|
Pool Notes: 1. Pool side phone is working. 2. Filter pressure gauge noted at 4psi. 3. Turnover rate=6.3 hours. 4. Pool water is clear. Inspection conducted by Scott Bradley,R.S. 732-7614 |