Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1696 | Volume (gallons): 52000 | Flow measure reading (gpm): 120 | Minimum required flow (gpm): 109 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 425 | Turnover Rate (min): 433 |
Total Chlorine (ppm): 0 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 160 | Pool water temp ˚F: 79 | pH: 8.2 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine levels did not meet minimum requirements
Make sure to add chlorine to meet sufficient levels and maintain proper levels when operating pool.
3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc)
Do not operate the pool when water clarity is poor. Ensure to fix water clarity issues prior to opening pool.
3701-31-04 (B)(1)(h) / Natural or artificial light shall be sufficient to see the pool bottom.
Critical Natural or artificial light was not sufficient to see the pool bottom
Do not operate the pool when there is not sufficient light to see the pool bottom.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Ensure pH is between 7.2-7.8 and maintained in this range prior to opening pool.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Ensure to correct issue prior to opening pool
Comments |
---|
Pool was not operating for public use at time of inspection. Pool operator arrived during inspection to remediate violations. Ensure to make bottom of pool visible and maintain proper disinfectant levels upon opening pool to public |