Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1696 Volume (gallons): 52000 Flow measure reading (gpm): Minimum required flow (gpm): 109
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 850 Turnover Rate (min): 480
Total Chlorine (ppm): 2.5 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 80 pH: 7.0 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A)(1) / Public swimming pool is licensed
Repeat The swimming pool license could not be located.
Post the 2018 Swimming Pool license.
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The two (2) main drain covers needed to be replaced in 2012.
Replace the main drain covers to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The two (2) main drain covers needed to replaced in 2012.
Replace the main drain covers to verify VGB compliance.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
The pool pH was noted at 7.0. Four (4) drops of Base Demand increased the pH to 7.2.
Increase and maintain the pool pH between 7.2-7.8. Correct By: 30-Jul-2018
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical The ACC unit pH reads 7.5. When tested, the pool pH was noted at 7.0.
Have the ACC unit serviced so the pool pH is accurate. Correct By: 30-Jul-2018
3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical Repeat The ACC unit alarm did not activate when tested.
Have the ACC unit serviced or replaced so that the audible or visual alarm is activated when necessary. Correct By: 30-Jul-2018
3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical Repeat The ACC unit would not function when tested.
Have the ACC unit serviced so the alarm will function when tested. Correct By: 30-Jul-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Periodic ACC unit alarm testing was not recorded.
Test, then record period ACC unit alarm testing in the pool records. Correct By: 30-Jul-2018


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 23-July-2018

The following violation(s) have been corrected since the last inspection.
Comments
Pool Notes:
1. The follow-up inspection scheduled for 7/6/18 was rescheduled.
2. The pool water is clear.
3. Proper safety equipment is available for use.
4. The report was emailed to Jacob Hooker.
Contact Scott Bradley,R.S. (732-7614) with any questions.