Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1696 | Volume (gallons): 52000 | Flow measure reading (gpm): 110 | Minimum required flow (gpm): 109 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 685 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 4 | Free Chlorine (ppm): 4 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 79 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The two (2) main drain covers were installed in 2005, and needed to be replaced in 2012.
Replace the two (2) main drain covers, or provide updated specifications to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The two (2) main drain covers were installed in 2005, and needed to be replaced in 2012.
Replace the two (2) main drain covers, or provide updated specifications to verify VGB compliance.
Comments |
---|
No other violations observed during the inspection. The pool otherwise Looks Great! Pool Notes: 1. Document periodic ACC unit alarm testing in pool records. 2. The pool water is clear. 3. Proper safety equipment is available for use. 4. ACC unit pH noted at 7.8. 5. The ACC unit alarm functions when tested. 6. Pool turnover rate=7.9 hours. 7. The report was emailed to Mr. Laney. Inspection conducted by Scott Bradley,R.S. 732-7614 |