Sampling Details | |||
---|---|---|---|
Sub Type: Hotel/motel | Special Feature: | Location: | |
Area: 490 | Volume (gallons): 12795 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 74 |
Disinfectant: Salt | Secondary Disinfectant: | ORP: 787 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 4 | Free Chlorine (ppm): 4 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 84 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The pool flow meter is not working.
Repair the flow meter so water turnover rates can be determined.
Comments |
---|
Pool Notes: 1. The water turnover rate could not be determined because the filter system flow meter was not working. 2. Pressure gauge noted at 15psi. 3. Auto Controller pH noted at 7.6. 4. The pool water is clear. Evaluation conducted by Scott Bradley,R.S. 732-7614 |