Sampling Details | |||
---|---|---|---|
Sub Type: Hotel/motel | Special Feature: | Location: | |
Area: 490 | Volume (gallons): 12795 | Flow measure reading (gpm): 43 | Minimum required flow (gpm): 27 |
Disinfectant: Salt | Secondary Disinfectant: | ORP: | Turnover Rate (min): 300 |
Total Chlorine (ppm): 3.5 | Free Chlorine (ppm): 3.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 82 | pH: 7.5 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter was not working.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. Ensure replacement flow meter has an appropriate range for the pool size (ideally between 0-100 gpm.) 3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical ORP value was not displayed on the ACC unit
Have the ACC unit serviced or replaced so that the ORP value is displayed 3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
Comments |
---|
-Pool looked clear from all points of the perimeter -Emergency phone was not working -All other safety equipment was provided and accessible -Please fix or replace the flow meter -Filter pressure was 10 psi -Pool temperature was recorded to be at 82 degF For questions or comments, please contact Sebastian Mejia (513-732-7612) |