Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1800 Volume (gallons): 54000 Flow measure reading (gpm): 120 Minimum required flow (gpm): 113
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 79 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A)(1) / Public swimming pool is licensed
The current Pool License is not posted. Post the current Pool License.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Updated information for the main drain covers has not been submitted to CCPH. Submit updated main drain cover information to verify VGB Compliance.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing from the skimmer baskets. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Updated information for the main drain covers has not been submitted to CCPH. Submit updated main drain cover information to verify VGB Compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 24-June-2019

Comments
No other violations observed during the inspection.
Pool Notes:
1. The pool water is clear.
2. Pool turnover rate noted at 7.5 hours.
3. One (1) lifeguard was on duty during the inspection.
4. The report was emailed to Mr. Henderson.
Contact Scott Bradley,R.S. (732-7614) with any questions.