Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 490 Volume (gallons): 12795 Flow measure reading (gpm): 45 Minimum required flow (gpm): 27
Disinfectant: Salt Secondary Disinfectant: ORP: 676 Turnover Rate (min): 284
Total Chlorine (ppm): 3 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0.5 Total Bromine (ppm): 0
Alkalinity (ppm): 110 Pool water temp ˚F: 81 pH: 7.3 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 05-April-2019

Comments
The disinfectant residuals and water quality parameters meet code requirement. The recommended range is 2-4 ppm. Make sure the free chlorine stays above 1.0 ppm.
-pH was measured at 7.3.
-All required safety equipment was provided.
-The pool perimeter was secure.
-The filter pressure was 10 psi.
-Turn over rate was 285 minutes.
- The facility uses salt and acid to create chlorine. Therefore the pool is disinfected using chlorine.
- ACC tests recorded monthly. Thanks.
- Pool records properly recorded.
- ORP at 676mv, pH on ACC at 7.40pH.

No violations noted. Keep up the good work. Ensure total chlorine is recorded daily.