Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Secondary Disinfectant: ORP: Turnover Rate (min):
Total Chlorine (ppm): Free Chlorine (ppm): Combined Chlorine (ppm): Total Bromine (ppm):
Alkalinity (ppm): Pool water temp ˚F: pH: Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat Equipment was replaced since last inspection. New ACC, chlorine feeder and pH feeder have been installed since last inspection.
Submit an equipment replacement notification form to the Ohio Dept. of Health for approval for the equipment change made.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Flow rate measured at 60 GPM; 74 GPM required for 8 hour turnover; must not exceed filter max flow capacity of 141.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter fence had gaps greater than 4 inches along the base of the green chain link fence.
Repair the base / bottom of the green chain link perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
3701-31-04 (D)(7)(d) / Flow or pressure switch for a shut off valve provided and unit is tested monthly
Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly. ACC failed to register an alarm or interrupt chlorine feed during simulated flow interruption.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Swimming alone is not recommended" sign(s) posted.
Post the "Swimming Alone is Not Recommended" sign(s) at all times the pool is available for use.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 11-July-2014

The following violation(s) have been corrected since the last inspection.
Comments
To avoid potential licensing action, the perimeter barrier (i.e. the green chain link fence) needs to be secured along the base of the fence so that no gaps in excess of four inches can be created. This need to be corrected by Friday, July 18, 2014.