Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1840 Volume (gallons): 62400 Flow measure reading (gpm): Minimum required flow (gpm): 130
Disinfectant: Secondary Disinfectant: ORP: 702 Turnover Rate (min): 480
Total Chlorine (ppm): 2.5 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 170 Pool water temp ˚F: 72 pH: 7.8 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm): 141
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Corrected During Inspection Equalizer line was not secured.
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation.
3701-31-04 (B)(1)(k) / Chemical storage or use shall not result in imminent health hazard.
Critical Corrected During Inspection Pool shock was stored above muriatic acid. Move chemicals so that they are not stored on top of eachother.

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. Flow meter is at the top because it only goes up to 100 gpm.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Corrected During Inspection Emergency device (telephone) has dial tone, but cannot dial 911.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-June-2019