Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1325 Volume (gallons): 39750 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Secondary Disinfectant: ORP: Turnover Rate (min):
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): Pool water temp ˚F: pH: 7.8 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection feeder was not properly plugged into ACC unit. Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat Documentation that ACC is properly working was only documented in May.
Ensure that ACC is documented monthly that it is being checked.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. No flow signal did come on when tested.
Replace sensors to ensure that no flow signal is properly working.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 09-July-2024

The following violation(s) have been corrected since the last inspection.
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Comments
Inspection Notes:
1. Informed by Mike from pool maintenance that the probe is on back order and it should be received by the end of the week for the ACC connection to the disinfectant feeder.
2. The pH was noted at 7.8.

Thank you!