Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1840 Volume (gallons): 62400 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 633 Turnover Rate (min):
Total Chlorine (ppm): 8 Free Chlorine (ppm): 8 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 130 Pool water temp ˚F: 75 pH: Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed ORP of 633.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat Flow meter observed to be too small to meet the capacity to accurately determine the flow rate.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 25-August-2022

Comments
Flow rate could not be determined; flow meter has not been replaced.
Ensure ACC is tested for August.