Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1650 Volume (gallons): 51000 Flow measure reading (gpm): 80 Minimum required flow (gpm): 106
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 690 Turnover Rate (min): 480
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 82 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The flow meter, and the filter pressure gauge do not appear to be working. Repair these items.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-July-2023

Comments
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.4.
3. All safety equipment is available.
4. ACC unit alarm is functioning. Testing is documented in pool records.
5. The report was emailed to Ms. Michelson.
Contact Scott Bradley, R.E.H.S. (732-7614) with any questions.