Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 2.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: 7.4 | pH: | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The main drain cover has passed the required replacement date.
Replace the cover to verify VGB compliance.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing in the skimmer baskets
Replace the missing weirs.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat The main drain cover has passed the required replacement date.
Replace the cover to verify VGB compliance.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(4)(a)(vi)/Total alkalinity is tested weekly The pool total alkalinity was not tested weekly. Test and record the pool total alkalinity at least once per week. Correct By: 21-Aug-2018 |
3701-31-04 (B)(4)(a)(vi)/Total alkalinity is tested weekly Total alkalinity was not tested weekly. Test and record the pool total alkalinity at least once each week. Correct By: 16-Aug-2018 |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 The pool pH was noted at 8.4. Three (3) drops of acid demand lowered the pH to 7.6. Lower and maintain the pool pH between 7.2-7.8. Correct By: 21-Aug-2018 |
3701-31-04 (E)(2)(d)/First aid kit provided Gloves were not provided in the first aid kit. Provide gloves for the first aid kit. Correct By: 16-Aug-2018 |
Comments |
---|
All other violations scheduled to be corrected, were corrected. Thanks! Pool Notes: 1. The follow-up inspection scheduled for 8/21/18 was rescheduled. 2. The report was emailed to Mr. Henke. Contact Scott Bradley,R.S. (732-7614) with any questions. |