Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): 130 | Minimum required flow (gpm): 113 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 525 | Turnover Rate (min): 415 |
Total Chlorine (ppm): 3.5 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0.5 | Total Bromine (ppm): |
Alkalinity (ppm): 190 | Pool water temp ˚F: 78 | pH: 8.3 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. 3701-31-04 (E)(3)(a) / "WARNING, NO LIFEGUARD", sign posted
The unguarded pool was in use without the "WARNING, NO LIFEGUARD" sign posted.
Post the WARNING, NO LIFEGUARD sign in a conspicuos location at all times the pool is available for use.
Comments |
---|
Ensure to repaint depth markers, none of them are visible Inspect ACC and ensure to raise ORP to minimum acceptable value No lifeguard on duty sign is not posted Pool chemicals are well balanced, pH is outside of acceptable limit Any questions please contact Michael at 513-560-6177 |