Sampling Details
Sub Type: Other Special Feature: Location:
Area: 3200 Volume (gallons): 137500 Flow measure reading (gpm): 475 Minimum required flow (gpm): 287
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 2.5 Free Chlorine (ppm): 2.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 81 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 424 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Corrected During Inspection The licensee /authorized representative was not keeping records on site .
All facility records must be maintained and available for review upon request. Lifeguard wrote records of test results on site.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Flow rate is greater than maximum flow rate for filters.
All equipment must be maintained in accordance with the manufacturers specifications. This could be due to recent backwashing.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 01-September-2015

Comments
Inspection notes:
- Proper safety equipment was provided.
- Pool water was clear.
- Total alkalinity is per operator's results.
- Cyanuric acid is not being used at this time.