Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1696 Volume (gallons): 52000 Flow measure reading (gpm): 70 Minimum required flow (gpm): 109
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 690 Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 87 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A)(1) / Public swimming pool is licensed
Repeat The 2019 Swimming Pool License could not be located. Post the 2019 Swimming Pool License.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 18-July-2019

Comments
No other violations observed during the inspection.
The pool otherwise Looks Great!
Pool Notes:
1. ACC unit alarm testing is documented in pool records. The alarm functions when tested.
2. The pool water is clear.
3. Proper safety equipment is available for use.
4. ACC unit pH noted at 7.5.
5. Pool turnover rate=12.4 hours. For an eight (8) hour turnover rate, the flow meter should read 109gpm.
6. Filter pressure gauges noted at 12 and 13psi.
7. The report was emailed to Mr. Doud.
Contact Scott Bradley,R.S. (732-7614) with any questions.