Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 1500 Volume (gallons): 42374 Flow measure reading (gpm): 80 Minimum required flow (gpm): 88
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 140 Pool water temp ˚F: 72 pH: 7.7 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
A new pump was installed and is not yet approved by ODH.
Submit the Equipment Replacement Notification Report to ODH for approval.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
The turnover rate was 8.8 hours. The turnover rate should be at least every 8 hours.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The outside filters and pump are accessible to unauthorized personnel.
Secure the outside filters and pump so that only authorized personnel have access.
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Repeat Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 11-June-2015

Comments
1. The disinfectant residuals and water quality parameters meet code requirements.
2. All required safety equipment was provided.
3. The pool perimeter is secure.
4. The required records are properly kept.
5. The turnover rate was 8.8 hours.
If you have any questions or concerns, call me at (513) 732-7612.