Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1650 Volume (gallons): 51000 Flow measure reading (gpm): 120 Minimum required flow (gpm): 110
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 785 Turnover Rate (min): 480
Total Chlorine (ppm): 2 Free Chlorine (ppm): 2 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 120 Pool water temp ˚F: 83 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Weirs are missing from the skimmers. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 05-August-2022

Comments
No other violations observed during the inspection.
The pool otherwise looks great!
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 7.4.
3. Turnover rate=7.1 hours.
4. Pool filter pressure gauge noted at 12psi.
4. All safety equipment is available.
5. ACC unit alarm functions when tested. Testing is documented in pool records.
6. The report was emailed to Swim Safe Pools.
Contact Scott Bradley, R.E.H.S. (732-7614) with any questions.