Sampling Details | |||
---|---|---|---|
Sub Type: School | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 65000 | Flow measure reading (gpm): 0 | Minimum required flow (gpm): 168 |
Disinfectant: Di/Tri-Chloro | Secondary Disinfectant: | ORP: 720 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 8 | Free Chlorine (ppm): 8 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 88 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 282 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) is functioning properly
Critical Repeat The ACC unit pH was noted at 7.9. Measured pH was 7.4.
Calibrate the ACC unit so the pool pH can be monitored accurately. Correct By: 28-Oct-2014 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
The filter system flow meter is not working.
Repair the flow meter so water turnover rates can be determined.
Comments |
---|
No other violations observed during the inspection. Pool Notes: 1. Filter pressure gauges noted at 13psi. 2. Auto Controller Alarm appears to be working properly. 3. The pool water is clear. 4. It is recommended the facility switch to Calcium Hypochlorite. Inspection conducted by Scott Bradley,R.S. 732-7614 |