Sampling Details | |||
---|---|---|---|
Sub Type: Camp | Special Feature: | Location: | |
Area: 1350 | Volume (gallons): 25000 | Flow measure reading (gpm): 40 | Minimum required flow (gpm): 62 |
Disinfectant: | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 2 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 70 | Pool water temp ˚F: 76 | pH: 7.2 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 62 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat Facility has made changes including, but not limited to the changes in decking, changes to your perimeter barrier (new sections and door), and changes to Backwash piping.
Facility has also changed Chlorinator.
Submit plans to Ohio Department of Health and have changes approved. Their phone number is (614) 644-7527 for environmental engineering. 3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative did not maintain records on site for review.
All facility records must be maintained and available for review upon request. 3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Pool railing and ladder were loose.
Secure railing and ladder. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Corrected During Inspection Three areas of fence could easily produce gaps greater than 6".
Perimeter barrier was repaired such that gaps greater than 6" could not be produced.
Comments |
---|
Inspection notes: - Discussed listed violations with operator on site. - Pool water was clear. |