Sampling Details | |||
---|---|---|---|
Sub Type: Camp | Special Feature: | Location: | |
Area: 1350 | Volume (gallons): 25000 | Flow measure reading (gpm): 55 | Minimum required flow (gpm): 52 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 454 |
Total Chlorine (ppm): 2.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 220 | Pool water temp ˚F: 70 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (D)(09) / Chemicals shall not be manually added to pool when bathers present.
Observed chlorine tablet in skimmer basket. Chlorine chemicals should not be manually added to the pool when bathers are present.
Stop adding chemicals to the pool when bathers are present.
Comments |
---|
Notes: -Pool was clear and met water chemistry requirements. -Safety equipment available. -Record log reviewed. Ensure to document that ACC and SVRS are checked monthly. -Door to club house was self closing but did not properly latching every time. Ensure that door properly closes all the way. |