Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 1 | Free Chlorine (ppm): 1 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications have not been provided for the two (2) main drain covers.
Provide specifications for the covers to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the two (2) main drain covers have not been provided.
Provide specifications for the covers to verify VGB compliance.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 The pool pH was noted at 8.2. Five drops of Acid Demand lowered the pH to 7.4. Lower and maintain the pool pH between 7.2-7.8. Correct By: 20-Jul-2017 |
Comments |
---|
All violations scheduled to be corrected were corrected. Thanks! 1. Due to weather, the reinspection scheduled for 7/20/17 was rescheduled. 2. Mr. Blume was contacted regarding the minimum free chlorine residual. 3. The report was emailed to Mr. Blume. Contact Scott Bradley,R.S. (732-7614) with any questions |