Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 1 Free Chlorine (ppm): 1 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications have not been provided for the two (2) main drain covers.
Provide specifications for the covers to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the two (2) main drain covers have not been provided.
Provide specifications for the covers to verify VGB compliance.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 02-August-2017

The following violation(s) have been corrected since the last inspection.
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
The pool pH was noted at 8.2. Five drops of Acid Demand lowered the pH to 7.4.
Lower and maintain the pool pH between 7.2-7.8. Correct By: 20-Jul-2017
Comments
All violations scheduled to be corrected were corrected.
Thanks!
1. Due to weather, the reinspection scheduled for 7/20/17 was rescheduled.
2. Mr. Blume was contacted regarding the minimum free chlorine residual.
3. The report was emailed to Mr. Blume.
Contact Scott Bradley,R.S. (732-7614) with any questions