Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1840 | Volume (gallons): 62400 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): | Free Chlorine (ppm): | Combined Chlorine (ppm): | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: | pH: | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not readable. The size of the flow meter is not the proper size to get an accurate reading. Flow meter needs to be able to read past 100gpm.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Comments |
---|
Flow meter unable to be read at time of inspection. Replace flow meter with one that has the capacity to properly read the flow rate of the pool. |