Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): 145 | Minimum required flow (gpm): 132 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 760 | Turnover Rate (min): |
Total Chlorine (ppm): 1.25 | Free Chlorine (ppm): 1.25 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): 0 |
Alkalinity (ppm): 120 | Pool water temp ˚F: 76 | pH: 7.7 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records prior to the pool company taking over (aquamarine). Records are now being kept by the pool company.
All facility records must be maintained and available for review upon request. 3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS/APSOS/ACC test results/ service records were not maintained. Please test and record the test in the pool log for both the ACC and Stingle Switch monthly and prior to opening. The ACC was tested during the inspection and observed to be properly working .
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. 3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate is not self closing and self latching. The pool was voluntarily closed by the operator. Ensure the gate is self closing and self latching prior to reopening the pool. A reinspection is necessary.
Ensure the gate is self closing and latching. 3701-31-04 (D)(09) / Chemicals shall not be manually added to pool when bathers present.
Corrected During Inspection Chlorine tablets were observed in the pool skimmer basket when swimmers were present. The tablets were removed. A reinspection is necessary to ensure the pool is properly disinfected.
Do not ever add chlorine tablets to the pool. 3701-31-04 (E)(2)(d) / First aid kit provided
First aid kit was missing a single use pair of gloves. Ensure gloves are provided.
Ensure gloves are provided. 3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat Corrected During Inspection "Swimming alone is not recommended" signs not posted.
Post the "Swimming Alone is Not Recommended" signs at all times the pool is available for use. The PIC created and posted a sign.
Comments |
---|
Notes -Pool was painted Ocean Blue (HRS90743 Porter Paints) which is not on the approved list. Ensure to contact the state to acquire a variance. -All safety equipment provided. Ensure phone is working at all times. -Pool water clear. -Water readings were code compliant. However, chlorine tablets were observed in the pool so a reinspection is necessary to ensure proper chlorine residuals are present. - A reinspection is also necessary for the non self closing gate. Pool was voluntarily closed. |