Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 1100 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): | Free Chlorine (ppm): | Combined Chlorine (ppm): | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: | pH: | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Observed the paint at the bottom of the wading pool to be deteriorating and chipping.
Recommend repainting/resurfacing the wading pool. Whenever a public swimming pool is repainted, resurfaces or a liner installed, the interior surface of the pool shall be white or an approved color unless the color is submitted to and approved by the director. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat Observed the existing flow meter's intended range to be between 20-100 GPM. Unable to determine rate-of-flow as flow rate at time of inspection was below meter's minimum intended range. A means of determining rate-of-flow shall be properly installed, provided and maintained on all water pumps so that the rate of circulation can be accurately determined.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. Recommend installed a low-flow range flow meter calibrated for type and size of piping so rate-of-flow can be determined. 3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat Observed the equipment and chemical storage shed to be unlocked at time of inspection. All equipment, chemical and other storage areas shall be maintained in a clean condition, free from any hazards and accessible only to authorized personnel.
Ensure the equipment and chemical storage shed is locked or otherwise maintained inaccessible to pool patrons. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. Observed the pH to be 8.4.
Treat the pool water so that the pH is within the acceptable range. 3701-31-04 (E)(2)(d) / First aid kit provided
Repeat Observed the first aid kit to be inside the equipment and chemical storage shed. Observed first aid kit with out minimum required supplies.
Ensure a first aid kit containing a minimum of gloves, gauze and bandages is provided pool side and accessible to pool patrons.
Comments |
---|
Unable to complete reinspection due to no person-in-charge at pool. Pool was gated, locked and sign posted informing patrons that pool is closed. Recommend pool is closed until reinspection is completed. Will follow-up. |