Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 150 Volume (gallons): 1000 Flow measure reading (gpm): 40 Minimum required flow (gpm): 8
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 626 Turnover Rate (min): 120
Total Chlorine (ppm): 0.4 Free Chlorine (ppm): 0.2 Combined Chlorine (ppm): 0.2 Total Bromine (ppm):
Alkalinity (ppm): 40 Pool water temp ˚F: 83 pH: 7.2 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 34 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat Corrected During Inspection ORP reading was below 650 mV.
Have the ACC unit inspected to determined why the ORP is low. ORP increased to >650 mV as chlorine residual rose above 2.0 ppm.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Flow rate exceeds filter capacity.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 14-August-2018

Comments
Water clarity, pH meet code requirements.
Records maintained.
Signage provided.
Perimeter barrier -OK.