Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): 110 Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 790 Turnover Rate (min): 322
Total Chlorine (ppm): 10 Free Chlorine (ppm): 10 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 78 pH: 7.2 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Observed sodium bicarbonate being stored on top of sealed boxes of acid as well as on top of the chlorine holding tank.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 29-June-2022

Comments
Inspection Notes:
1. Pool water observed clear.
2. Chlorine noted at 10ppm.
3. All safety equipment easily accessible.
4. Ensure that chemicals are properly stored to prevent chemical reactions.