Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): 80 | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 740 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 2 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 110 | Pool water temp ˚F: 80 | pH: 7.7 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat The first aid kit was in the equipment room.
Place the first aid kit on the pool deck so it is available for emergencies.
Comments |
---|
No other violations observed during the inspection. The Pool otherwise Looks Great! Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.7. 3. The pool pH was between 7.6-7.8. 4. Pool turnover rate=7.4 hours. 5. Filter pressure gauge noted at 12psi. 6. Some effort was required when an an attempt was made to have the entrance gate latch when closing. Mr. Blume was contacted to adjust the gate. 7. The 2016 Swimming Pool license is posted. 8. The report was emailed to Mr. Blume. 9. ACC alarm functions when tested. Inspection conducted by Scott Bradley,R.S. 732-7614 |