Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1000 Volume (gallons): 30000 Flow measure reading (gpm): 60 Minimum required flow (gpm): 60
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 606 Turnover Rate (min): 480
Total Chlorine (ppm): 4 Free Chlorine (ppm): 4 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 120 Pool water temp ˚F: 84 pH: 7.5 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 75 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading is above 650 mv
The ACC unit ORP was noted at 606mv.
Increase the ACC unit ORP to 650mv minimum. Correct By: 23-Jul-2014
3701-31-04 ( D )(6)(a) / ORP reading is above 650 mv
ORP reading was noted at 606 mv.
Increase the ACC unit ORP to 650mv minimum. Correct By: 23-Jul-2014
3701-31-04 (B)(1)(a) / Outlet covers are installed/secured/in compliance
Critical Specifications are not available for the two (2) main drain covers.
Provide specifications (Manufacturer, Model#, Install and Replacement dates) for the main drain covers. Correct By: 23-Jul-2014
3701-31-04 (D)(7)(c) / Audible/visual alarm when unit is malfunctioning or when pH or ORP levels are not acceptable.
The ACC unit alarm could not be tested.
Determine a way to test the ACC unit alarm. Correct By: 23-Jul-2014
3701-31-04 (D)(7)(c) / Audible/visual alarm when unit is malfunctioning or when pH or ORP levels are not acceptable.
The ACC unit alarm could not be tested.
Determine a way to test the ACC unit alarm. Correct By: 23-Jul-2014
3701-31-04 (E)(2)(d) / First aid kit provided
First aid kit does not have sufficient items to control bleeding or disposable gloves.
Provide these items in the first aid kit. Correct By: 23-Jul-2014


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 09-July-2014

Comments
Pool Notes:
1. Turnover rate=8 hours.
2. ACC unit pH noted at 7.3
3. The pool pH was between 7.4-7.6
4. The pool water was clear
Inspection conducted by Scott Bradley,R.S. 732-7614