Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): 80 | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 710 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 2 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 84 | pH: 7.5 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
Repeat A throw line was not available for the life ring.
Provide a 30-60 foot throw line for the life ring. Correct By: 25-Aug-2017
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.5. The pool pH was between 7.4-7.6. 3. Pool turnover rate=7.4 hours. 4. Filter pressure gauge noted at 6psi. 5. ACC unit testing is documented in the pool records. 6. Post the 2017 Swimming Pool License. 7. The report was emailed to Mr. Blume. Contact Scott Bradley,R.S. (732-7614) with any questions |