Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1800 Volume (gallons): 54000 Flow measure reading (gpm): 80 Minimum required flow (gpm): 113
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 675
Total Chlorine (ppm): 0.6 Free Chlorine (ppm): 0.6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 210 Pool water temp ˚F: 79 pH: 8.0 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Ensure turnover rates do not exceed 480 minutes
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm.
Ensure disinfection residual is at or exceeds 1ppm.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 30-June-2022

Comments
Inspection Notes:
1. Pool water observed clear.
2. Ensure that the flotation device has a throw line of at least 30ft.
3. Ensure chlorine levels are at or exceed 1ppm.
4. Ensure flow rate is at or exceeds 113 gpm.

Thank you!