Sampling Details
Sub Type: Camp Special Feature: Location:
Area: 1350 Volume (gallons): 25000 Flow measure reading (gpm): 75 Minimum required flow (gpm): 62
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 6 Free Chlorine (ppm): 6 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 78 pH: 7.6 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 62 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Flow rate was higher than maximum flow rate for filter.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention device on hose was missing.
Have the backflow prevention device replaced so that backflow is prevented.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 07-June-2016

Comments
Inspection notes:
- Pool water was clear.
- Spine board, shepherds crook, first aid kit, and emergency phone were provided.
- Provide air gap for fill hose until backflow prevention device can be provided.