Sampling Details | |||
---|---|---|---|
Sub Type: Camp | Special Feature: | Location: | |
Area: 1350 | Volume (gallons): 25000 | Flow measure reading (gpm): 75 | Minimum required flow (gpm): 62 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 78 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 62 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Flow rate was higher than maximum flow rate for filter.
All equipment must be maintained in accordance with the manufacturers specifications. 3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention device on hose was missing.
Have the backflow prevention device replaced so that backflow is prevented.
Comments |
---|
Inspection notes: - Pool water was clear. - Spine board, shepherds crook, first aid kit, and emergency phone were provided. - Provide air gap for fill hose until backflow prevention device can be provided. |