Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1840 | Volume (gallons): 62400 | Flow measure reading (gpm): 45 | Minimum required flow (gpm): 130 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 78 | pH: 7.4 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
A new disinfection system was installed.
Submit an Equipment Replacement Notification form for the disinfection system to the Ohio Department of Health for review and approval. 3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Turn over rate with flow rate of 45 GPM is insufficient. Turn over rate is 23 hours and 6.6 minutes.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Railing to main stairs is loose.
Secure Railing. 3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. Throw line was broken in places because it was brittle.
Provide a proper floatation device at all times. Replace throw line.
Comments |
---|
Inspection notes: Records were well kept and included monthly testing of ACC. (Thank you!) Pool water was clear. Signs were appropriate. First aid kit and phone were provided and visible. (First aid kit had sufficient means to stop bleeding and disposable gloves) |