Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): 110 Minimum required flow (gpm): 74
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 725 Turnover Rate (min): 323
Total Chlorine (ppm): 0.2 Free Chlorine (ppm): 0.2 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 110 Pool water temp ˚F: 82 pH: 7.8 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm. Reading during the inspection was 0.2 ppm.
Operator added chlorine during the inspection and the final reading was 1.0 ppm free chlorine.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 10-June-2024

Comments
Inspection Notes:
Pool was operating at 0.2 ppm chlorine. PIC added chlorine and the final reading was 1.0 ppm.
Ensure chlorine level remains above 1.0 ppm.