Sampling Details | |||
---|---|---|---|
Sub Type: School | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 65000 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 755 | Turnover Rate (min): |
Total Chlorine (ppm): 1 | Free Chlorine (ppm): 1 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): | Pool water temp ˚F: | pH: 8.0 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater. ORP reading was below 650 mv Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. Chlorine disinfectant residual was less than 1 ppm for the pool. Pool was closed at time of inspection. Re-inspection to ensure properly residual. Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm. Pool free chlorine disinfectant residual was below 1 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. |
Comments |
---|
-Record books were being maintained. -Minimum disinfection residual was met code requirments. Recommended to be at 2ppm-4ppm. -Ensure pH is maintained at 7.2-7.9. |