Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): 140 | Minimum required flow (gpm): 132 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): |
Total Chlorine (ppm): 1.75 | Free Chlorine (ppm): 1.75 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 110 | Pool water temp ˚F: 79 | pH: 7.3 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Disinfection system was not operating properly at the time of the inspection. The disinfectent system was not operating.
Do not operate the pool when disinfection system is not operating properly. Ensure that the disinfection system is functioning properly prior to placing the pool back into operation. 3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection residuals were not tested daily at pool side and at the required intervals for pools. Total chlorine was not being tested.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. Make sure to test for free and total chlorine. 3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications, skimmer weirs were missing.
All equipment must be maintained in accordance with the manufacturers specifications, Make sure to replace each of the missing skimmer weirs. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps, one of the flow meters was broken.
Properly replace the broken flow meter or have a pump curve available for every water pump used for the pool. 3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Corrected During Inspection Equalizer lines were not plugged or covered pool side.
The PIC properly plugged the equalizer lines in the skimmer basket. 3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected. 3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
Repeat Corrected During Inspection 12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The sheperds hook was stored in a locked shed.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times. The PIC placed the sheperds hook in the pool area so patrons may use it if necessary. 3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
Corrected During Inspection A back/spine board without a head immobilizer and straps was not provided at the unguarded pool. The backboard was stored in a locked shed not available to patrons.
Provide the back/spine board at the pool at all times. The PIC correctly placed the backboard in the pool area.