Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1650 | Volume (gallons): 51000 | Flow measure reading (gpm): 110 | Minimum required flow (gpm): 110 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 730 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 80 | pH: 7.5 | Cyanuric acid (ppm): 10 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
Comments |
---|
No violations observed during this inspection. Thank you. Notes: Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time. Restrooms clean and supplied. ACC flow switch tested during inspection. Flow switch functions properly at this time. Signage and safety equipment provided as required. REMINDER: Record all data in weekly pool operation reports as required. Pool was open at the time of the inspection. |