Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 1615 Volume (gallons): 63447 Flow measure reading (gpm): 95 Minimum required flow (gpm): 132
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 775 Turnover Rate (min): 667
Total Chlorine (ppm): 7 Free Chlorine (ppm): 7 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 84 pH: 8.1 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Flow meter should be reading at least 132 gpm, read 95 at time of inspection.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed to be 8.1
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 28-July-2020