Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1000 Volume (gallons): 30000 Flow measure reading (gpm): 80 Minimum required flow (gpm): 63
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 669 Turnover Rate (min): 375
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: 73 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Observed pipe in pump room leaking into bucket.
Ensure leak is repaired.
3701-31-04 (B)(6)(l) / Secondary means of entrapment/evisceration prevention is provided
Observed the equalizer line in skimmer basket by basket ball hoop to not be plugged.
Ensure that equalizer line is plugged by re-inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 21-June-2023

Comments
Notes:
-Safety equipment available.
-Pool clear and meets code requirements.
-Reinspection to ensure that equalizer line by basket ball hoop is plugged.