Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1325 | Volume (gallons): 39750 | Flow measure reading (gpm): 85 | Minimum required flow (gpm): 83 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 700 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 2 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 80 | Pool water temp ˚F: 79 | pH: 7.5 | Cyanuric acid (ppm): 70 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladder on the side of the pool where the woods are was not secured to the pool deck.
Repair or replace the ladder so that they are in good repair.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gate door was not self-closing and lockable.
Repair gates door in order to be self-closing and lockable. Correct By: 14-Aug-2018
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level is at 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -All required safety equipment was provided. - Pool gate was not self latching. -The pool perimeter was secure. -The filter pressure was 20 psi. -The pool water was clear. If you have any questions or concerns, call Mackinzie Dickman at (513) 732-7602. |