Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1500 | Volume (gallons): 42374 | Flow measure reading (gpm): 85 | Minimum required flow (gpm): 88 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 5 | Free Chlorine (ppm): 5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 78 | pH: 7.3 | Cyanuric acid (ppm): 20 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Chlorine feed pump has been changed from a Flex Flo A1N30A-6T to a Stenner 85M5.
Please submit an Equipment Replacement Notification Report (ERNR) to the Ohio Department of Health. ERNR can now be submitted and paid for online via the Ohio Dept. of Health's website: www.odh.ohio.gov. 3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat Swimming pool records do not include any weekend readings, even though the pool was open.
Record weekend water (free and combined chlorine, pH, and water temperature and water clarity readings. The pool should not be open for use if it has not been tested. 3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection residuals were not tested daily at pool side at the required intervals for pools without automatic chemical controllers (ACC).
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. 3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat pH was not tested daily at pool side at required intervals for pools without automatic chemical controllers(ACC).
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. 3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. 3701-31-04 (B)(4)(a)(ix) / Chemicals added to the pool other than those used for disinfection
Repeat Chemicals added to the pool other than those used for disinfection were not being recorded.
Facility records must indicate when chemicals, other than disinfectants, are added to the pool water. 3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
The throw rope attached to the USCG Type IV personal flotation device was not 30-60 feet in length as required at this unguarded pool.
Provide and attach a 30 -60 foot length of throw rope to the flotation device so that drowning swimmers can be safely rescued wtithout putting the rescuer's life in jeopardy.
Comments |
---|
Facility inspection notes: Water clarity, disinfectant residuals, and water quality readings meet minimum code requirements at this time. Signage and safety equipment provided. Restrooms are clean and properly supplied. |