Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 836 | Volume (gallons): 25080 | Flow measure reading (gpm): 60 | Minimum required flow (gpm): 53 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 418 |
Total Chlorine (ppm): 2 | Free Chlorine (ppm): 2 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 110 | Pool water temp ˚F: 74 | pH: | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter barrier had gaps greater than 4 inches. Construction being done; about 50% of the fencing has been removed and temporary fencing is in place; gaps that equaled 8 inches, 12 inches, and 19 inches in some places observed. Secure the perimeter barrier so that no gaps greater than four inches exist to prevent unauthorized access. It is recommende that the operator voluntarily closes the pool until an approved perimeter barrier is in place.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
Comments |
---|
Inspection Notes: 1. Water chemistry noted at proper levels. 2. Perimeter barrier not secure due to construction. It is recommended that the operator voluntarily close the pool until an approved perimeter barrier is in place. Pool closed at time of inspection. Will follow up with facility for how to submit information to the state for approval. 3. Gaps greater than four inches observed in alterations to pool barrier. |