Sampling Details
Sub Type: Hotel/motel Special Feature: Location:
Area: 418 Volume (gallons): 12500 Flow measure reading (gpm): 50 Minimum required flow (gpm): 26
Disinfectant: Salt Secondary Disinfectant: ORP: 620 Turnover Rate (min): 250
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1 Combined Chlorine (ppm): 0.5 Total Bromine (ppm):
Alkalinity (ppm): 60 Pool water temp ˚F: 80 pH: 7.5 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat Records did not have dates on them. Ensure date are made on sheets to confirm that readings are being done daily and maintained for at least two years.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results/ service records were not maintained.
Document that ACC is being tested monthly.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 21-December-2023

Comments
Notes:
-Emergency equipment available.
-Emergency phone properly working.
-Ensure that records are properly being dated. Records should be maintained for 2 years.
-Ensure that combined chlorine does note exceed 1.