Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1160 Volume (gallons): 35500 Flow measure reading (gpm): Minimum required flow (gpm):
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 760 Turnover Rate (min): 480
Total Chlorine (ppm): Free Chlorine (ppm): 10 Combined Chlorine (ppm): Total Bromine (ppm):
Alkalinity (ppm): 100 Pool water temp ˚F: pH: 8.2 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications have not been provided for the two (2) main drain covers.
Provide specifications for the covers to verify VGB compliance.
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the two (2) main drain covers have not been provided.
Provide specifications for the covers to verify VGB compliance.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
The pool pH was noted at 8.2. Five drops of Acid Demand lowered the pH to 7.4.
Lower and maintain the pool pH between 7.2-7.8. Correct By: 20-Jul-2017


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Follow-up

[?] Inspection Date: 14-July-2017

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required.
The pool free chlorine residual was noted at 0.5ppm. The pool free chlorine residual was noted at 0.6ppm.
Increase and maintain the pool free chlorine residual at 1.0ppm minimum. Correct By: 14-Jul-2017
3701-31-04 (D)(7)(c)/Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
When tested, the ACC unit alarm did not function.
Repair the ACC unit so it will function when tested. Correct By: 14-Jul-2017
3701-31-04 (E)(2)(a)(ii)/A USCG Type IV personal flotation device with 30 -60 foot throw line provided
The throw line was missing from the life ring.
Provide a 30-60 foot throw line for the life ring. Correct By: 14-Jul-2017
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm.
Pool free chlorine disinfectant residual was noted at 0.5ppm. Pool free chlorine disinfectant residual was noted at 0.6ppm.
Increase and maintain the pool free chlorine residual at 1.0ppm minimum. Correct By: 14-Jul-2017
Comments
All other violations corrected.
Thanks!
Pool Notes:
1. The pool water is clear.
2. ACC unit pH noted at 8.
3. ACC unit alarm is functioning.
4. The report was emailed to Mr. Blume.
Contact Scott Bradley,R.S. (732-7614) with any questions