Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1160 | Volume (gallons): 35500 | Flow measure reading (gpm): 100 | Minimum required flow (gpm): 74 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 820 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 0.6 | Free Chlorine (ppm): 0.6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 82 | pH: 7.2 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 141 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (A)(1) / Public swimming pool is licensed
Repeat The current Swimming Pool License is not posted.
Post the 2018 Swimming Pool License.
3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
No soap is available in the men's rest room.
Provide soap in the men's rest room. Correct By: 27-Aug-2018
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Specifications for the two (2) main drain covers could not be located.
Provide specifications for the main drain covers to verify VGB compliance.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat The pool free chorine residual was noted at 0.6ppm.
Increase and maintain the free chlorine residual at 1.0ppm minimum. Correct By: 27-Aug-2018
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical Repeat Specifications for the two (2) main drain covers could not be located.
Provided specification for the drain covers to verify VGB compliance.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was noted at 0.6ppm.
Increase and maintain the free chlorine residual at 1.0ppm minimum. Correct By: 27-Aug-2018
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.4 3. Pool turnover rate=5.9 hours. 4. Filter pressure gauge noted at 10psi. 5. ACC unit testing is recorded in the pool records. 6. ACC unit alarm functions when tested. 7. The report was emailed to Ms. Butts. Contact Scott Bradley,R.S. (732-7614) with any questions |