Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 100 | Volume (gallons): 780 | Flow measure reading (gpm): | Minimum required flow (gpm): 6.5 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 723 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 1.5 | Free Chlorine (ppm): 1.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 60 | Pool water temp ˚F: 86 | pH: 7.4 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 74 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Observed no Automatic chemical controller (ACC) test records maintained on site for the last 30 days.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. Ensure ACC is tested at least once a month and results are recorded on site. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. Flow was too low to determine the rate-of-flow for the wading pool.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Comments |
---|
Inspection notes: - Pool water was clear. - Flow meter was reading <40 gpm on 40-140 gpm flow meter. - Less than 30 ppm Cyanuric acid was noted. |